Alat panyalindungan lonjakan arus (SPD) nyaéta alat anu penting pisan pikeun panyalindungan kilat dina alat éléktronik. Ieu dianggo pikeun ngawatesan tegangan kaleuleuwihan instan tina saluran listrik sareng saluran transmisi sinyal kana rentang tegangan anu tiasa ditahan ku alat atanapi sistem, atanapi Arus kilat anu kuat ngalir ka taneuh pikeun ngajaga alat atanapi sistem anu dijaga tina dampak sareng karusakan.
| IEC Listrik | 150 | 275 | 320 | 385 | 440 | ||
| Tegangan AC Nominal (50/60Hz) | 120V | 230V | 230V | 230V | 400V | ||
| Tegangan Operasi Kontinyu Maksimum (AC) | (LN) | Uc | 150V | 275V | 320V | 385V | 440V |
| (N-PE) | Uc | 255V | |||||
| Arus Pangosongan Nominal (8/20μs) | (LN)/(N-PE) | In | 10kV/10kA | ||||
| Arus Pangosongan Maksimum (8/20μs) | (LN)/(N-PE) | Imax | 20kA/20kA | ||||
| Tingkat Protéksi Tegangan | (LN)/(N-PE) | Up | 0.6kV/1.5kV | 1.3kV/1.5kV | 1.5kV/1.5kV | 1.5kV/1.5kV | 1.8kV/1.5kV |
| Turutan Rating Interrupt Ayeuna | (N-PE) | Ifi | 100 LEUNGEUN | ||||
| Waktos Tanggapan | (LN)/(N-PE) | tA | <25ns/<100ns | ||||
| Sekering Cadangan (maks) | 125A gL /gG | ||||||
| Rating Arus Sirkuit Pendek (AC) | (LN) | ISCCR | 10kA | ||||
| TOV Tahan 5 detik | (LN) | UT | 180V | 335V | 335V | 335V | 580V |
| TOV 120 menit | (LN) | UT | 230V | 440V | 440V | 440V | 765V |
| modeu | Tahan | Gagal Aman | Gagal Aman | Gagal Aman | Gagal Aman | ||
| TOV Tahan 200ms | (N-PE) | UT | 1200V | ||||
| Rentang Suhu Operasi | -40ºF nepi ka +158ºF[-40ºC nepi ka +70ºC] | ||||||
| Kalembaban Operasi anu Diidinan | Ta | 5%…95% | |||||
| Tekanan atmosfir sareng ketinggian | RH | 80k Pa..106k Pa/-500m..2000m | |||||
| Torsi Sekrup Terminal | Mmax | 39,9 lbf-in [4,5 Nm] | |||||
| Penampang Konduktor (maks) | 2 AWG (Padet, Terdampar) / 4 AWG (Fleksibel) | ||||||
| 35 mm² (Padet, Teruntai) / 25 mm² (Fleksibel) | |||||||
| Pemasangan | Rel DIN 35 mm, EN 60715 | ||||||
| Tingkat Perlindungan | IP 20 (dipasang) | ||||||
| Bahan Perumahan | Termoplastik: Gelar Pamadaman UL 94 V-0 | ||||||
| Protéksi Termal | Muhun | ||||||
| Kaayaan Operasi / Indikasi Kasalahan | Héjo ok / Beureum cacad | ||||||
| Kapasitas Kontak Jarak Jauh (RC) / Switching RC | Pilihan | ||||||
| Penampang Konduktor RC (maks) | AC: 250V/0.5A;DC:250V/0.1A;125V/0.2A;75V/0.5A | ||||||
| 16 AWG (Padet) / 1.5 mm² (Padet) | |||||||