CJ: Kode perusahaan
M: Diwangun kasus circuit breaker
1: Desain No
□: Dipeunteun ayeuna pigura
□: Kode karakteristik kapasitas ngarecah/S ngalambangkeun tipe baku (S bisa dileungitkeun)H ngalambangkeun tipe luhur
Catetan: Aya opat jenis kutub nétral (kutub N) pikeun produk opat fase. Kutub nétral tipe A teu dilengkepan unsur tripping leuwih-ayeuna, na salawasna dihurungkeun, sarta teu dihurungkeun atawa pareum babarengan jeung lianna. tilu kutub.
Kutub nétral tipe B teu dilengkepan unsur tripping leuwih-ayeuna, sarta eta dihurungkeun atawa pareum babarengan jeung tilu kutub séjén (kutub nétral dihurungkeun saméméh switching off) Kutub nétral tipe C dilengkepan over- elemen tripping ayeuna, tur dihurungkeun atawa dipareuman bareng jeung tilu kutub séjén (kutub nétral dihurungkeun saméméh dipareuman) Kutub nétral tipe D dilengkepan unsur tripping leuwih-ayeuna, éta salawasna dihurungkeun tur teu switched. on atawa off babarengan jeung tilu kutub séjén.
Ngaran aksésori | Pelepasan éléktronik | Pelepasan sanyawa | ||||||
Kontak bantu, dina tegangan release, kontak alam | 287 | 378 | ||||||
Dua set kontak bantu, kontak alarm | 268 | 368 | ||||||
Shunt release, kontak alarm, kontak bantu | 238 | 348 | ||||||
Dina release tegangan, kontak alarm | 248 | 338 | ||||||
Kontak bantu kontak alarm | 228 | 328 | ||||||
Shunt ngaleupaskeun kontak alarm | 218 | 318 | ||||||
Kontak bantu di handapeun-tegangan release | 270 | 370 | ||||||
Dua set kontak bantu | 260 | 360 | ||||||
Kaluaran shunt ngaleupaskeun tegangan handap | 250 | 350 | ||||||
Shunt ngaleupaskeun kontak bantu | 240 | 340 | ||||||
Kaluaran tegangan handap | 230 | 330 | ||||||
Kontak bantu | 220 | 320 | ||||||
Kaluaran shunt | 210 | 310 | ||||||
Kontak alarm | 208 | 308 | ||||||
Taya aksésori | 200 | 300 |
1 Nilai dipeunteun tina circuit breakers | ||||||||
Modél | Imax (A) | Spésifikasi (A) | Dipeunteun Tegangan Operasi (V) | Dipeunteun Insulasi Tegangan (V) | Icu (kA) | ICs (kA) | Jumlah Kutub (P) | Jarak Busur (mm) |
CJMM1-63S | 63 | 6,10,16,20 25,32,40, 50,63 | 400 | 500 | 10* | 5* | 3 | ≤50 |
CJMM1-63H | 63 | 400 | 500 | 15* | 10* | 3,4 | ||
CJMM1-100S | 100 | 16,20,25,32 40,50,63, 80.100 | 690 | 800 | 35/10 | 22/5 | 3 | ≤50 |
CJMM1-100H | 100 | 400 | 800 | 50 | 35 | 2,3,4 | ||
CJMM1-225S | 225 | 100.125, 160.180, 200.225 | 690 | 800 | 35/10 | 25/5 | 3 | ≤50 |
CJMM1-225H | 225 | 400 | 800 | 50 | 35 | 2,3,4 | ||
CJMM1-400S | 400 | 225.250, 315.350, 400 | 690 | 800 | 50/15 | 35/8 | 3,4 | ≤100 |
CJMM1-400H | 400 | 400 | 800 | 65 | 35 | 3 | ||
CJMM1-630S | 630 | 400.500, 630 | 690 | 800 | 50/15 | 35/8 | 3,4 | ≤100 |
CJMM1-630H | 630 | 400 | 800 | 65 | 45 | 3 | ||
Catetan: Lamun parameter test pikeun 400V, 6A tanpa release pemanasan |
2 Karakteristik operasi putus waktos tibalik nalika unggal kutub pelepasan arus langkung pikeun distribusi kakuatan diaktipkeun dina waktos anu sami | ||||||||
Item tés Ayeuna (I/In) | Daérah waktos tés | kaayaan awal | ||||||
Non-tripping ayeuna 1.05In | 2h(n>63A),1h(n<63A) | kaayaan tiis | ||||||
Tripping ayeuna 1.3In | 2h(n>63A),1h(n<63A) | Teraskeun geura sanggeus tés No.1 |
3 Karakteristik operasi putus waktos tibalik nalika unggal kutub over- release ayeuna keur panyalindungan motor diaktipkeun dina waktos anu sareng. | ||||||||
Nyetel waktos Konvensional Ayeuna kaayaan Awal | Catetan | |||||||
1.0Di | > 2 jam | Kaayaan tiis | ||||||
1.2 Dina | ≤2h | Neruskeun langsung saatos tés No.1 | ||||||
1,5 Dina | ≤4 mnt | Kaayaan tiis | 10≤Dina≤225 | |||||
≤8 mnt | Kaayaan tiis | 225≤Dina≤630 | ||||||
7.2 Dina | 4s≤T≤10s | Kaayaan tiis | 10≤Dina≤225 | |||||
6s≤T≤20s | Kaayaan tiis | 225≤Dina≤630 |
4 Karakteristik operasi sakedapan tina circuit breaker pikeun distribusi kakuatan bakal diatur salaku 10in + 20%, sarta salah sahiji circuit breaker pikeun panyalindungan motor bakal diatur salaku 12ln ± 20% |
CJMM1-63, 100, 225, Outline sareng Ukuran Instalasi (Sambungan papan hareup)
Ukuran (mm) | Kodeu modél | |||||||
CJMM1-63S | CJMM1-63H | CJMM1-63S | CJMM1-100S | CJMM1-100H | CJMM1-225S | CJMM1-225 | ||
Ukuran Outline | C | 85.0 | 85.0 | 88.0 | 88.0 | 102.0 | 102.0 | |
E | 50.0 | 50.0 | 51.0 | 51.0 | 60.0 | 52.0 | ||
F | 23.0 | 23.0 | 23.0 | 22.5 | 25.0 | 23.5 | ||
G | 14.0 | 14.0 | 17.5 | 17.5 | 17.0 | 17.0 | ||
G1 | 6.5 | 6.5 | 6.5 | 6.5 | 11.5 | 11.5 | ||
H | 73.0 | 81.0 | 68.0 | 86.0 | 88.0 | 103.0 | ||
H1 | 90.0 | 98.5 | 86.0 | 104.0 | 110.0 | 127.0 | ||
H2 | 18.5 | 27.0 | 24.0 | 24.0 | 24.0 | 24.0 | ||
H3 | 4.0 | 4.5 | 4.0 | 4.0 | 4.0 | 4.0 | ||
H4 | 7.0 | 7.0 | 7.0 | 7.0 | 5.0 | 5.0 | ||
L | 135.0 | 135.0 | 150.0 | 150.0 | 165.0 | 165.0 | ||
L1 | 170.0 | 173.0 | 225.0 | 225.0 | 360.0 | 360.0 | ||
L2 | 117.0 | 117.0 | 136.0 | 136.0 | 144.0 | 144.0 | ||
W | 78.0 | 78.0 | 91.0 | 91.0 | 106.0 | 106.0 | ||
W1 | 25.0 | 25.0 | 30.0 | 30.0 | 35.0 | 35.0 | ||
W2 | - | 100.0 | - | 120.0 | - | 142.0 | ||
W3 | - | - | 65.0 | 65.0 | 75.0 | 75.0 | ||
Pasang Ukuran | A | 25.0 | 25.0 | 30.0 | 30.0 | 35.0 | 35.0 | |
B | 117.0 | 117.0 | 128.0 | 128.0 | 125.0 | 125.0 | ||
od | 3.5 | 3.5 | 4.5 | 4.5 | 5.5 | 5.5 |
CJMM1-400,630,800, Outline sareng Ukuran Instalasi (Sambungan papan payun)
Ukuran (mm) | Kodeu modél | |||||||
CJMM1-400S | CJMM1-630S | |||||||
Ukuran Outline | C | 127 | 134 | |||||
C1 | 173 | 184 | ||||||
E | 89 | 89 | ||||||
F | 65 | 65 | ||||||
G | 26 | 29 | ||||||
G1 | 13.5 | 14 | ||||||
H | 107 | 111 | ||||||
H1 | 150 | 162 | ||||||
H2 | 39 | 44 | ||||||
H3 | 6 | 6.5 | ||||||
H4 | 5 | 7.5 | ||||||
H5 | 4.5 | 4.5 | ||||||
L | 257 | 271 | ||||||
L1 | 465 | 475 | ||||||
L2 | 225 | 234 | ||||||
W | 150 | 183 | ||||||
W1 | 48 | 58 | ||||||
W2 | 198 | 240 | ||||||
A | 44 | 58 | ||||||
Pasang Ukuran | A1 | 48 | 58 | |||||
B | 194 | 200 | ||||||
Od | 8 | 7 |
Balik Board Connection Cut-kaluar Diagram Colokkeun
Ukuran (mm) | Kodeu modél | ||||||
CJMM1-63S CJMM1-63H | CJMM1-100S CJMM1-100H | CJMM1-225S CJMM1-225H | CJMM1-400S | CJMM1-400H | CJMM1-630S CJMM1-630H | ||
Ukuran Balik Board Connection Tipe Colokkeun | A | 25 | 30 | 35 | 44 | 44 | 58 |
od | 3.5 | 4,5*6 liang jero | 3.3 | 7 | 7 | 7 | |
od1 | - | - | - | 12.5 | 12.5 | 16.5 | |
od2 | 6 | 8 | 8 | 8.5 | 9 | 8.5 | |
oD | 8 | 24 | 26 | 31 | 33 | 37 | |
oD1 | 8 | 16 | 20 | 33 | 37 | 37 | |
H6 | 44 | 68 | 66 | 60 | 65 | 65 | |
H7 | 66 | 108 | 110 | 120 | 120 | 125 | |
H8 | 28 | 51 | 51 | 61 | 60 | 60 | |
H9 | 38 | 65.5 | 72 | - | 83.5 | 93 | |
H10 | 44 | 78 | 91 | 99 | 106.5 | 112 | |
H11 | 8.5 | 17.5 | 17.5 | 22 | 21 | 21 | |
L2 | 117 | 136 | 144 | 225 | 225 | 234 | |
L3 | 117 | 108 | 124 | 194 | 194 | 200 | |
L4 | 97 | 95 | 9 | 165 | 163 | 165 | |
L5 | 138 | 180 | 190 | 285 | 285 | 302 | |
L6 | 80 | 95 | 110 | 145 | 155 | 185 | |
M | M6 | M8 | M10 | - | - | - | |
K | 50.2 | 60 | 70 | 60 | 60 | 100 | |
J | 60.7 | 62 | 54 | 129 | 129 | 123 | |
M1 | M5 | M8 | M8 | M10 | M10 | M12 | |
W1 | 25 | 35 | 35 | 44 | 44 | 58 |
Dina MCCB, dipeunteun kapasitas pegatna sirkuit pondok nujul kana kapasitas megatkeun dina kaayaan nu tangtu.Saatos prosedur tés anu ditangtukeun, kedah diperhatoskeun yén pemutus sirkuit terus mawa arus anu dipeunteun na.Pikeun nyumponan kabutuhan pangguna anu béda-béda, seueur pabrik pemutus sirkuit ayeuna ngabagi kapasitas pegatna sirkuit pondok tina rating cangkang anu sami dina tingkat anu béda, sareng pangguna tiasa milih pemutus sirkuit anu pas dumasar kana kabutuhanna tina minimum dugi ka maksimal. circuit breakers ayeuna.Éta pisan umum tur kapanggih dina ampir sagala wangunan atawa struktur nu aranjeunna mindeng dicokot for teu dibales.Tapi, aranjeunna maénkeun peran anu penting dina sistem jaringan listrik urang sareng kedah dijaga pikeun ngajaga standar kaamanan anu pang anyarna.
MCCBs nyadiakeun respon sakedapan ka arus sesar circuit pondok, dumasar kana prinsip éléktromagnétik.MCCB ngandung hiji coil solenoid nu dibangkitkeun médan éléktromagnétik leutik lamun ayeuna ngaliwatan MCCB nu.MCCB ngagunakeun alat anu sénsitip suhu (unsur termal) sareng alat éléktromagnétik anu sénsitip ayeuna (unsur magnét) pikeun nyayogikeun mékanisme perjalanan (magnét termal) pikeun tujuan panyalindungan termal sareng isolasi.Salila operasi normal atawa kaayaan normal, médan éléktromagnétik dihasilkeun ku coil solenoid téh negligible.Nanging, nalika aya gangguan sirkuit pondok dina sirkuit, arus ageung mimiti ngalir kana solenoid sareng, salaku hasilna, médan éléktromagnétik anu kuat diadegkeun anu narik bar perjalanan sareng muka kontak.