Standar | IEC / EN 60898-1 | ||||
Kutub No | 1P,1P+N, 2P, 3P,3P+N,4P | ||||
tegangan dipeunteun | AC 230V / 400V | ||||
Dipeunteun Ayeuna (A) | 20A,25A,32A,40A,50A,63A,80A,100A,125A | ||||
Lengkungan tripping | C, D | ||||
Kapasitas sirkuit pondok dipeunteun (lcn) | 10000A | ||||
Kapasitas sirkuit pondok jasa dipeunteun (ICs) | 7500A | ||||
Frékuénsi dipeunteun | 50/60Hz | ||||
Dipeunteun dorongan tahan tegangan Uimp | 6kV | ||||
Terminal sambungan | Terminal tihang kalawan clamp | ||||
Daya tahan éléktro-mékanis | Ins100=10000:n125=8000 | ||||
Jangkungna Sambungan Terminali | 20 mm | ||||
Kapasitas sambungan | Konduktor fléksibel 35mm² | ||||
Konduktor kaku 50mm² | |||||
Pamasangan | Dina rel simetris DIN 35mm | ||||
Pamasangan panel |
Tés | Tipe Tripping | Test Ayeuna | Kaayaan Awal | Waktos tripping atanapi Non-tripping Time Provider | |
a | Waktos-reureuh | 1.05 Dina | Tiis | t≤1h(Dina≤63A) t≤2h(ln>63A) | Taya Tripping |
b | Waktos-reureuh | 1.30 Dina | Sanggeus tés a | t<1h(Dina≤63A) t<2h(Di>63A) | Ngajanteng |
c | Waktos-reureuh | 2 Dina | Tiis | 10s 20s63A) | Ngajanteng |
d | Sakedapan | 8 ln | Tiis | t≤0.2s | Taya Tripping |
e | instan | 12 Dina | Tiis | t <0.2s | Ngajanteng |
Lamun hiji MCB tunduk kana kontinyu leuwih-arus, strip bimetallic heats up na bends.Kancing éléktromékanis dileupaskeun nalika MCB ngalieurkeun jalur bi-logam.Nalika pangguna nyambungkeun jepitan éléktromékanis ieu kana mékanisme kerja, éta muka kontak pemutus microcircuit.Akibatna, éta ngabalukarkeun MCB pareum sareng ngeureunkeun arus anu ngalir.Pamaké kudu individual switch on MCB pikeun mulangkeun aliran ayeuna.Alat ieu ngajaga tina cacad anu disababkeun ku arus kaleuleuwihan, kaleuleuwihan, sareng sirkuit pondok.